CLICK HERE TO GO TO 7010B, THE REPLACEMENT UNIT
The BRK hardwired smoke alarm with photoelectric sensor is designed to reduce common "nuisance" alarms. It's an excellent choice for installations in or near kitchens, near fireplaces, or in hallways directly outside bathrooms, utility rooms, or other areas prone to steam. This alarm is also a popular choice for hotel/motel applications.
The 7010 AC-powered smoke alarm with photoelectric sensor includes these features:
Photoelectric sensor which is more effective at detecting smoldering fires which smolder for hours before bursting into flame.
120-volt AC inter-connectable (with maximum 18 compatible devices). The alarm can be interconnected with up to 12 other compatible smoke alarms and six compatible devices like bells, horns, repeaters and door closers. If one unit triggers an alarm, all smoke alarms in the series will sound. Power indicators show which unit in the series initiated the alarm.
Quick plug-in power connector for easy installation.
Alarm indication which in an interconnected system, automatically identifies which unit initiated the alarm.
Optipath 360 technology allows 360-degree access to the layer of air on the ceiling or wall that carries the fire signatures (smoke, combustion particles and volatile components).
Single test/silence button which both silences a non-threatening alarm or low battery warning and allows you to test the unit's functionality.
Locking feature for tamper resistance.
10-year limited warranty.
SPECS:
10-Years Limited Warranty
Model #7010
Weight6.7
oz
Dimension5.0"
dia x 2.1"H
Operating Voltage120V
AC 60Hz
Operating Current.045
amps (standby/alarm)
Temperature Range40°F
(4°C) to 100°F (38°C)
Humidity Range10%
to 90% relative humidity (RH)
Audio Alarm85dB
at 10 feet
Test/SilenceElectronically
simulates smoke condition, causing the unit to alarm Press and hold
test/silence button
Alarm ResetAutomatic
when smoke clears
InterconnectionsUp
to 18 units of First Alert or BRK Smoke, CO and Heat Alarms. Maximum of 12
smoke alarms. See user's manual for details.
Smoke SensorPhotoelectric
Indicator Lights/Sounds
AC Power: Constant
Green LED
Local Alarm: Red
LED flashes rapidly
Remote Alarm: Red
LED out.
ListingListed
to UL217 Standard