***DISCONTINUED, LINK TO NEW ALARM BELOW***
Click here --> BRK First Alert 7020BSL <--Click here
The First Alert BRK Model Number 7010BSL is a hardwired photoelectric smoke alarm with integrated 177 candela strobe light. The First Alert 7010BSL not only has the ADA approved strobe light but the best smoke detection you can get, Photoelectric. The 7010BSL also has smart strobe technology which will pulse in different rates to tell you if you have smoke or carbon monoxide. YOU MUST HAVE A CO DETECTOR within your system and interconnected to this unit for that to work. If you are deaf or simply have some hearing loss the 7010BSL is your best option to protect your home. The First Alert 7010BSL is specifically designed for residential and institutional applications including sleeping rooms of hospitals, hotels, motels, dormitories and other multifamily dwellings as defined in standard NFPA 101. Model 7010BSL complies with UL217, UL1971, CSFM, NFPA 72, HUD, FHA and other agencies that model their codes after the above agencies. They meet building codes where AC with battery backup, silence, photoelectric smoke alarms are required. The alarms are interconnectable with up to 18 devices, of which 12 can be smoke alarms. One device includes both a strobe light and photoelectric smoke alarm and only requires one electrical box. Saves installation time.
SPECS: Model # 7010BSL 177 CANDELA XENON STROBE. Powerful 177 candela xenon strobe light provides effective visual warning to hearing impaired residents.
1 Hz FLASH RATE. 60 fl ashes per minute rate meets ADA, ANSI 117.1 NFPA 72 and UL1971 requirements for visual signal devices.
OPTIPATH 360 TECHNOLOGY. Provides 360 degrees of direct access to the smoke sensing chamber.
BATTERY BACKUP.Two AAA batteries provide backup for the smoke alarm during power outages. (Note: will not power the strobe light).
Weight 10.9 oz Dimension 5.1" dia x 4.0"H Operating Voltage 120V AC 60Hz w/ two AAA battery backup for smoke alarm (Note: will not power the strobe light).
Voltage Range: 108V AC to 132V AC
Operating Current 0.05/0.60 amps (standby/alarm) Temperature Range 40°F (4°C) to 100°F (38°C)
Humidity Range 10% to 90% relative humidity (RH) Audio Alarm 85dB at 10 feet Test/Silence Electronically simulates smoke condition, causing the unit to alarm Press and hold test/silence button
Alarm Reset Automatic when smoke clears Interconnections Up to 18 units of First Alert or BRK Smoke, CO and Heat Alarms. Maximum of 12 smoke alarms. See user's manual for details. Smoke Sensor Photoelectric Strobe Light 177 candela Xenon strobe
Flash Rate: 1 Hz.
Smoke Alarm: Constant approx. 1 fl ash per second
CO Alarm: Intermittent approx. 1 flash per second for four flashes, then 5 seconds off. Pattern is repeated.
Indicator Lights/Sounds
AC Power: Constant Green LED
DC Power: Intermittent Red LED
Local Alarm: Red LED flashes rapidly